Rated Voltage: 12kV / 24kV
Insulation Level:
12kV: Power frequency withstand voltage 42kV; Lightning impulse withstand voltage 75kV (Breaking port: 48kV / 85kV)24kV: Power frequency withstand voltage 65kV; Lightning impulse withstand voltage 125kV
Applicable Standards: IEC 60298, GB 3906
Rated Current & Short Circuit Withstand
12kV Standard Type
Busbar Rated Current: 630A ~ 4000ACircuit Breaker Rated Current: 630A ~ 4000AContactor Rated Current: 400AShort-time Withstand Current (4s): 25kA, 31.5kA, 40kAPeak Withstand Current: 63kA, 80kA, 100kAEarthing Switch Withstand Capacity: 40kA/4sInternal Arc Withstand Level: 40kA/1s
24kV Standard Type
Rated Current: 630A, 1250A, 2500AShort-time Withstand Current (4s): 25kA, 31.5kAEarthing Switch Withstand Capacity: 31.5kA/4sInternal Arc Withstand Level: 31.5kA/1s
MVnex 550 Compact / MVnex 500 Ultra-compact
Rated Voltage: 12kVShort-time Withstand Current: ≤31.5kAPeak Withstand Current: ≤80kAMain Circuit Resistance: ≤100μΩ
Cabinet Dimension (Width × Depth × Height, mm)
12kV Standard Cabinet
Width: 650 / 800 / 1000Height: 2250Depth: 1400 / 1600
MVnex 550 Compact Type
Size: 550 (W) × 2250 (H) mmWeight: 400–700kgFloor space reduced by over 40% compared with traditional switchgear
MVnex 500 Ultra-compact Type
Cabinet width only 500mmWall-mounted installation available; front operation passage only 1mReduce substation construction area by 60%Maintenance-free throughout the whole life cycle
If you have any questions, please feel free to send us an email or call us, and we will do our best to solve them for you
حق چاپ @Shiny-Control Technology Develop (beijing) Co., Ltd.