VEP-12 Indoor VCB with Embedded Pole

The VEP indoor solid-embedded vacuum circuit breaker is the world’s first full-range solid-embedded vacuum circuit breaker developed by Xiamen Huadian Switchgear Co., Ltd., covering voltage ratings of 12kV, 24kV and 40.5kV.

Featuring high-performance, low-resistance vacuum interrupters, the VEP vacuum circuit breaker achieves fully solid-embedded insulation after epoxy resin casting, and is completely maintenance-free over its service life.

Rated Voltage: 12 kV, 17.5 kV, 24 kV, 40.5 kV

Rated Insulation Level (Unit: kV)

  • Auxiliary Circuit Power Frequency Withstand Voltage: 2 kV
  • Power Frequency Withstand Voltage (1min):
  • 12kV: 42 kV
  • 17.5kV: 42 kV
  • 24kV: 50/65 kV**
  • 40.5kV: 95 kV

Lightning Impulse Withstand Voltage (Peak):

  • 12kV: 75 kV
  • 17.5kV: 95 kV
  • 24kV: 125 kV
  • 40.5kV: 185 kV

Rated Frequency:

  • 12kV: 50 Hz
  • 17.5kV: 50/60 Hz
  • 24kV: 50 Hz
  • 40.5kV: 50 Hz

Rated Current (Unit: A)

  • 12kV: 630A, 1250A, 1600A, 2000A, 2500A, 3150A, 4000A*, 5000A*
  • 17.5kV: 630A, 1250A, 1600A, 2000A, 2500A, 3150A, 4000A*
  • 24kV: 630A, 1250A, 1600A, 2000A, 2500A, 3150A, 4000A*
  • 40.5kV: 1250A, 1600A, 2000A, 2500A, 3150A, 4000A*

Rated Short-Circuit Breaking Current (Unit: kA)

  • 12kV: 20kA, 25kA, 31.5kA, 40kA, 50kA
  • 17.5kV: 31.5kA, 40kA
  • 24kV: 25kA, 31.5kA, 40kA
  • 40.5kV: 25kA, 31.5kA, 40kA

Rated Short-Time Withstand Current (Unit: kA)

Rated Short-Circuit Making Current (Peak, Unit: kA)

  • 12kV: 50kA, 63kA, 80kA, 100kA (125kA), 125kA (150kA)
  • 17.5kV: 80kA, 100kA
  • 24kV: 63kA, 80kA, 100kA
  • 40.5kV: 63kA, 80kA, 100kA

Rated Peak Withstand Current (Unit: kA)

Rated Short-Circuit Current Duration (Unit: s)

  • 12kV: 4s
  • 17.5kV: 3s
  • 24kV: 3/4s**
  • 40.5kV: 4s